![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_0.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_1.jpg)
Scope of certification
This Certification Programme applies to selected ranges of Air Handling Units.
Participants shall certify all models in the selected product range up to the maximum stated air flow.
A range to be certified shall include at least one size with a rated air volume flow below 7 m³/s (25 000 m³/h).
Certification requirements
For the qualification procedure: the selection software will be audited by our internal auditor. A visit on production site will be organized. During that visit, the auditor will select one real unit per range, as well as several model boxes that will cover all mechanical variations.
The selected models will be tested and performances delivered by the selection software will be compared to the performances measured in an independent laboratory.
For the repetition procedures, the auditor will annually check the software conformity against the production data, and tests will be repeated every 3 to 6 years
Certified characteristics & tolerances
- External Pressure: 4% or 15 Pa
- Absorbed motor power: 3%
- Heat recovery efficiency: 3%-points
- Heat recovery pressure drop (air side):
max. of 10% or 15 Pa
- Water coil performances (heating/cooling): 2%
- Water coil pressure drop (water side):
max. of 10% or 2 kPa
- Radiated sound power level casing: 3 dB(A)
- Sound power level unit openings:
− 5dB@125 Hz
− 3dB@250 – 8 000 Hz
ECC Reference documents
- Certification manual
- Operational Manual OM-5
- Rating Standard RS 6/C/005
Scope of certification
This Certification programme applies to selected ranges of Air to Air Plate andTube Heat Exchangers. Participants shall certify all models in the selected range, including:
- cross flow, counter-flow and parallel flow units
- all sizes
- all materials
- all airflow rates
- all edge lengths
Heat Exchangers with accessories such as bypass and dampers shall not be included.
The programme does not cover other types of Air to Air Heat Exchangers like Rotary Heat Exchangers or Heat Pipes. Combination of units (twin exchangers) shall not be included.
Certification requirements
For each range to be certified, 3 units will be selected by Eurovent Certification and tested in an independent Laboratory.
On a yearly basis, Eurovent Certification checks whether the certified products still fulfil the requirements. One unit selected from regular production will be tested in an independent laboratory. If the previous test campaign has been successfully completed and the unit of the current test campaign is ready for a new test, the certification is granted for another year.
Certified characteristics & tolerances
- Dimensions: ± 2 mm
- Plate spacing: ± 1% or ± 1 plate
- Dry efficiency: −3 percentage points
- Wet efficiency: −5 percentage points
- Pressure drop: +10%, minimum 15 Pa
ECC Reference documents
- Certification manual
- Operational Manual OM-8
- Rating Standard RS 8/C/001
Testing standards
•EN 308
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_6.jpg)
Scope of certification
Eurovent Air to Air Rotary Heat Exchangers Certification Programme applies to all Rotary Heat Exchangers including casing. Participants shall certify all models, if available, including:
- all classes: condensation rotor / non hygroscopic rotor / enthalpy rotor / hygroscopic rotor / sorption rotor
- all rotor geometry (wave height, foil thickness)
- all sizes (rotor diameters and rotor depths)
- all materials
- all airflow rates
- all different types of sealing (if available)
Certification requirements
For the qualification & repetition procedures: one unit will be selected and tested by an independent laboratory.
Certified characteristics & tolerances
- Sensible Efficiency: −3% points
- Latent Efficiency: −5% points (min. tolerance
- 0.2 g/kg in absolute humidity of leaving supply air).
- Pressure Drop: −110% (min 10 Pa)
ECC Reference documents
- Certification manual
- Operational Manual OM-10
- Rating Standard RS 8/C/002
Scope of certification
This Certification Programme applies to all Active and Passive Chilled Beams.
Chilled Beams are presented by ranges but all ranges must be certified. This applies to all product ranges which have either catalogue leaflets with product details including technical data or similar product information in electronic format.
Certification requirements
For the qualification & repetition procedures (yearly): 3 units are selected from regular production and tested in the independent Laboratory selected by Eurovent Certification.
Obtained performances shall be compared with the values presented in the catalogues or electronic selection from manufacturer’s website.
Certified characteristics & tolerances
Cooling capacity: 3 conditions are required.
- Active: 80 – 100 – 120% of the nominal air flow rate.
- Passive: 8 – 10 – 12°C temperature difference.
ECC Reference documents
- Certification manual
- Operational Manual OM-12
- Rating Standard RS 2/C/007
Testing standards
- EN 14518: “Testing and rating of Passive Chilled Beams”
- EN 15116: “Testing and rating of Active Chilled Beams”
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_12.jpg)
Scope of certification
This Certification Programme applies to factory-made units intended for Close Control Air Conditioning. This programme includes units with cooling capacities up to 100 kW under the specified test conditions.
Participating companies must certify all production models within the scope of the programme.
Certification requirements
For the qualification & repetition procedures: 10% of the units declared will be selected and tested by an independent laboratory.
Certified characteristics & tolerances
Air-Cooled and Water-Cooled Close Control Air Conditioners
- Total cooling capacity (−8%)
- Sensible cooling capacity (−8%)
- EER (−8%)
- A-weighted sound power level (+0 dB)
Chilled-Water Close Controls Air Conditioners
- Total cooling capacity (−8%)
- Sensible cooling capacity (−8%)
- Effective power input (+8%)
- A weighted sound power level (+0 dB)
- Water pressure drop (+10%)
ECC Reference documents
- Certification manual
- Operational Manual OM-1
- Rating Standard RS 6/C/001
- Rating Standard RS 6/C/004
- Rating Standard RS 6/C/006
Testing standards
- EN 14511
- EN 12102 - EUROVENT 8/1
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_13.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_14.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_15.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_16.jpg)
Scope of certification
This certification programme includes:
- AC1: comfort units with cooling capacity up to 12 kW
- AC2: comfort units with cooling capacity from 12 to 45 kW
- AC3: comfort units with cooling capacity from 45 to 100 kW
This programme applies to factory-made units intended to produce cooled air for comfort air conditioning (AC1, AC2, AC3). It also applies to units intended for both cooling and heating by reversing the cycle. For the AC1 programme class G units are excluded.
Participating Companies must certify all production models within the scope of the programme they enter. However concerning multi-split air conditioners, only systems with maximum two indoor units are included.
Certification requirements
For the qualification & repetition procedures: 10% of the units declared will be selected and tested by an independent laboratory.
Certified characteristics & tolerances
- Capacity (cooling and heating) −5%
- Efficiency (EER and COP) −8%
- A-weighted sound power level +0 dB
ECC Reference documents
- Certification manual
- Operational Manual OM-1
- Rating Standard RS 6/C/001
- Rating Standard RS 6/C/004
- Rating Standard RS 6/C/006
Testing standards
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_17.jpg)
Certified characteristics & tolerances
- Capacity (cooling, sensible, heating): −5%
- Water pressure drop: +10%
- Fan power input: +10%
- A-weighted sound power: +1 / +2 dB(A)
- Air flow rate: -10%
- Available static pressure 0 Pa for medium speed and −5 Pa for other speeds
- FCEER & FCCOP
- Eurovent energy efficiency class
ECC Reference documents
- Certification manual
- Operational Manual OM-1A
- Rating Standard RS 6/C/002
- Rating Standard RS 6/C/002A
Testing standards
• Performance testing: Eurovent 6/3, 6/11, 6/10
• Acoustic testing: Eurovent 8/2
Scope of certification
- This Certification Programme applies to Fan Coil Units using hot or chilled water. It concerns both non ducted and ducted fan coils:
- Non ducted units: Fan Coil Units with air flow less than 0.7 m³/s and a published external static duct pressure at 40 Pa maximum.
- Ducted units: Fan Coil Units up to 1 m³/s
airflow and 300 Pa available pressure.
- Participating companies must certify all
production models within the scope of the
programme.
Certification requirements
•Repetition procedure: the number of units to be tested each year will be proportional to the number of his basic models listed in the Directory, in an amount equal to 20% for Fan Coil Units with a minimum of one test.
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_18.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_19.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_20.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_21.jpg)
The first ECC / CTI collaborative certification program for Cooling Towers
The Eurovent Certification Company (ECC, Brussels, Belgium) is pleased to announce the Certification programme for cooling tower thermal performance developed in cooperation with the Cooling Technology Institute Est.1950 (CTI, Houston, Texas, USA). The scope of the program includes standardized model lines for open circuit cooling towers, typically factory assembled. Standardized model lines are composed of individual models that are required to have published thermal rating capacities at corresponding input fan power levels.
Thermal performance certification via this program offers a tower buyer assurance that the capacity published for the product has been confirmed by the initial and on-going performance testing per the requirements of the program using CTI STD-201. It also offers for regulators of energy consumption related to cooling towers, that the capacity of the towers has been validated. Minimum energy efficiency standards such as ASHRAE 90.1, which requires cooling tower energy efficiency validation by the CTI certification process, are used by governments and by green building certification programs such as LEED™.
Scope of certification
The Eurovent Certification Programme for Cooling Towers applies to product ranges (or product lines) of Open-Circuit series Cooling Towers. The programme applies to product ranges that:
- Are manufactured by a company whose
headquarter or main facility are located in
Europe, Middle-East, Africa or India. After
getting the Eurovent Certification, the CTI
certificate could be requested.
- Have already achieved and hold current certification by the Cooling Technology Institute (CTI) according to CTI STD-201.
Certification requirements
For the qualification & repetition procedures (yearly): our internal auditor will visit the production place and review the conformity of Data of Records. One unit per range will be selected and tested by an independent test agency.
Certified characteristics & tolerances
- Certified characteristic shall be per CTI STD-201
- Entering wet bulb temperature:
−12.8°C to 32.2°C (55°F to 90°F)
- Cooling range > 2.2°C (4°F)
- Cooling approach > 2.8°C (5°F)
- Process fluid temperature < 51.7°C (125°F)
- Barometric pressure:
−91.4 to 105.0 kPa (27” to 31” Hg)
ECC Reference documents
- Certification manual
- Operational Manual OM-4
- Rating Standard RS 9/C/001
Scope of certification
The Eurovent Certification Programme for Drift Eliminators applies to Drift Eliminators used for evaporative water-cooling equipment.
Certified characteristics & tolerances
The following characteristics of Drift Eliminators shall be certified by tests:
- For counter-flow and cross-flow film fill, the average drift losses of the two tests at 3.5 m/s are less than 0.007% of circulating water flow rate.
- For cross-flow splash fill, the average drift losses of the two tests at 3 m/s are less than 0.007% of circulating water flow rate.
No tolerance will be applied on the average drift losses.
ECC Reference documents
- Certification manual
- Operational Manual OM-14
- Rating Standard RS 9/C/003
Scope of certification
- This programme applies to standard chillers and hydronic heat pumps used for heating, air conditioning and refrigeration.
- They may operate with any type of compressor (hermetic, semi-hermetic and open) but only electrically driven chillers are included.
- Only refrigerants authorised in EU are considered. Chillers may be air cooled, liquid cooled or evaporative cooled.
Certification requirements
Qualification and repetition: a certain number of units will be selected by Eurovent Certification and tested every year, based on the number of ranges and products declared.
Scope of certification
- This Certification Programme applies to air filters elements rated and sold as “Medium or Fine Air Filters F5-F9” as defined in EN 779:2012 and with a front frame size of 592 x 592 mm according to standard EN 15805.
- When a company joins the programme, all
relevant air filter elements shall be certified.
Certification requirements
•For the qualification & repetition procedures: 4 units will be selected and tested by an independent Laboratory selected by Eurovent Certification.
Certified characteristics & tolerances
- Filter class: no tolerance.
- Initial pressure drop: +10% + 5 Pa (minimum 15 Pa)
- Initial efficiency for F7 to F9: 10% – point
- Discharge efficiency for F7 to F9: 10% – point
- Eurovent energy class: no tolerance
- Annual energy consumption
ECC Reference documents
- Certification manual
- Operational Manual OM-11
- Rating Standard RS 4/C/001
Testing standards
• EN 779:2012
• Eurovent 4/11
Certified characteristics & tolerances
- Cooling & heating capacity and EER & COP at full load: < −5%
- A-weighted sound power level: > +3 dB(A)
- Water pressure drop: +15%
- Available pressure: −15%
ECC Reference documents
- Certification manual
- Operational Manual OM-3
- Rating Standard RS 6/C003
- Rating Standard RS 6/C/003A
Testing standards
- Performance testing: EN 14511
- Sound testing: EN 12102
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_31.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_32.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_33.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_34.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_35.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_36.jpg)
Scope of certification
The Eurovent Certification Programme for Heat Exchangers applies to products using axial flow fans. The following products are excluded from the Eurovent Certification Programme for Heat Exchangers:
- Products units using centrifugal type fans.
- Units working at 60 Hz
In particular, the following products are also excluded from the Eurovent Certification programme for Dx Air Coolers and Air Cooled Condensers:
• Products using R717 refrigerant (ammonia), CO2, and refrigerants with high glide like R407C or without correction factors.
Air coolers for refrigeration
Dry coolers
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_37.jpg)
Air cooled condensers
- Product ranges of Dx Air Coolers where
maximum standard SC2 is below 1.5 kW.
- Product ranges of Air Cooled Condensers where maximum standard capacity under DT1 15K is below 2.0 kW
Certification requirements
- Qualification: units selected by Eurovent Certification shall be tested in an Independent Laboratory selected by Eurovent Certification.
- Repetition procedure: units selected from regular production shall be tested on a yearly basis.
Certified characteristics & tolerances
- Standard capacity -8%
- Fan power input +10%
- Air volume flow ±10%
- External surface area ±4%
For Air Cooled Condensers and Dry Coolers:
- A-weighted sound pressure level: +2 dB(A)
- A-weighted sound power level: +2 dB(A)
- Surface area: ±4%
ECC Reference documents
- Certification manual
- Operational Manual OM-2
- Rating Standard RS 7/C/003
- Rating Standard RS 7/C/001
Testing standards
- Performance ENV 328
- Performance EN 327
- Acoustics EN 13487
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_38.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_39.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_40.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_41.jpg)
Scope of certification
- This programme applies to standard chillers and hydronic heat pumps used for heating, air conditioning and refrigeration.
- They may operate with any type of compressor (hermetic, semi-hermetic and open) but only electrically driven chillers are included.
- Only refrigerants authorised in EU are considered. Chillers may be air cooled, liquid cooled or evaporative cooled.
Certification requirements
Qualification and repetition: a certain number of units will be selected by Eurovent Certification and tested every year, based on the number of ranges and products declared.
Certified characteristics & tolerances
- Cooling & heating capacity and EER & COP at full load: < −5%
- A-weighted sound power level: > +3 dB(A)
- Water pressure drop: +15%
- Available pressure: −15%
ECC Reference documents
- Certification manual
- Operational Manual OM-3
- Rating Standard RS 6/C003
- Rating Standard RS 6/C/003A
Testing standards
- Performance testing: EN 14511
- Sound testing: EN 12102
- At least two references per basic model group representing 80% of sales shall be declared.
- One Bill of Material for each declared reference.
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_42.jpg)
Certification requirements
- Qualification: sampling and test of one unit & Audit of one factory.
- Repetition test of one unit per brand every 6 months & Annual audit of each factory.
Certified characteristics & tolerances
- Warmest and coldest product temp. ±0.5°C
- Refrigeration duty (kW) 10%
- Evaporating temperature −1°C
- Direct elec. Energy Consumption +5%
- Refrigeration elec. Energy Cons.
- Total Display Area (TDA) −3%
ECC Reference documents
- Certification manual
- Operational Manual OM-7
- Rating Standard RS 14/C/001
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_43.jpg)
Scope of certification Testing standards Scope of certification
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_44.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_45.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_46.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_47.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_48.jpg)
- This Certification Program applies to air-cooled and water cooled rooftops rated below 100 kW.
- Models with cooling or heating capacity ranging from 100 kW to 200 kW can be certified as an option.
- Models of rooftops using gas burners for heating shall be only certified for cooling.
Certification requirements
•For the qualification and repetition procedures (yearly) between 1 & 3 units are selected and tested by Eurovent Certification, depending on the number of products declared.
Certified characteristics & tolerances
- Capacity (Cooling or Heating): −5%
- EER or COP: -8%
- Condenser water pressure drop: +15%
- A-weighted Sound Power Level: +3 dBA.
- Eurovent Energy Efficiency class (cooling and heating)
ECC Reference documents
- Certification manual
- Operational Manual OM -13
- Rating Standard RS 6/C/007
Testing standards
- EN 14511 for Performance Testing
- EN 12102 for Acoustical Testing
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_49.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_51.jpg)
Scope of certification
The certification programme for Variable Refrigerant Flow (VRF) applies to:
- Outdoor units used in Variable Refrigerant Flow systems with the following characteristics:
- Air or water source,
• Reversible, heating-only and cooling-only. VRF systems with data declared and published as combinations are excluded from the scope. Heat recovery units are included in the scope but the heat recovery function is not certified.
High ambient systems are included in the scope but tested under standard conditions as specified in RS 6/C/008.
Certification requirements
• Qualification: units selected by Eurovent Certification shall be tested in an independent laboratory selected by Eurovent Certification.
• Repetition procedure: units selected from regular production shall be tested on a yearly basis.
Certified characteristics & tolerances
- Outdoor Capacity (cooling and heating): −8%
- Outdoor Efficiency (EER, COP): −10%
- A-weighted sound power level: 0 dB
ECC Reference documents
- Certification manual
- Operation manual OM-15
- Rating Standard RS 6/C/008
- Rating Standard RS 6/C/009
Testing standards
• EN 14511
• EN 12102
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_52.jpg)
![](/fileadmin/REHVA_Journal/Dynamic_chapters/images/p49-58_Eurovent_Certification_Programmes_RJ1302_img_53.jpg)